R-11
Features
■ High Surge Energy: Up to 1800 J
■ Reflection Measurement
■ Multiple Pre-locating Methods:
-Low Voltage Pulse Method
-ICM (impulse current method )
-ARM Measurement( Arc reflection method)
-X-axis Auxiliary Locating Method
■ All-in-one Design
■ Locating Distance: Up to 100km
Description
The R-11 Cable Fault Locator is mainly composed of R-11
HV (High Voltage) Generator and TDR-RT Time Domain Reflectometer, including various
Pre-location methods, such as low voltage pulse method, ICM (impulse current method ), ARM
measurement( Arc reflection method), X-axis method auxiliary locating method. It can resolve
the malfunctions and locate the fault points, which contains low resistance, high resistance,
intermittent, flashover,leak and disconnection fault on various cables of 380V, 6KV, 10KV, 35KV,
110KV, 220kV.
TDR-RT reflection method can locate disconnected and low resistance faults, which is also able
to measure the full length of the cable or correct the wave speed. Big wheels make it easy for
customer to use at any site.
Application
■ Rail Transit
■ Power Grid
■ Power Plant
■ Petrochemical
■ Cable Plant
■ New Energy
■ Metallurgy
R-11 HV Generator
Output Surge Voltage 0~30kV (Continuous adjustable)
Ronaldo Time Domain Reflectometer
Measurement Range 0~100km
Resolution 0.4m
Accuracy ±0 .2%L (m) (V=160m/μs)
Pulse Width 50ns~10μs
Language Chinese/English
Rechargeable Battery 3.5 hours
Sampling Rate 200MHz
Wave Velocity 100~300m/μs
Memor y More than 1000
Display 6”Color Screen 800×600
Cable Voltage 380V-220kV
Maximum Burning Energy 800W
Maximum Burning Current 30mA
Capacitance 4μF
Maximum Single Surge 1800J
Insulation Testing 2kΩ—10MΩ
Operation Temperature -15℃~50 ℃
Dimension 45.6cm × 51.2cm × 111.5cm
Weight 86 kg
Power Supply 220V15%,1 kVA
Rotection Degree IP53